Complete distribution switchgear KRP-10 VA-630...3150 U3, T3
- Pick-up from the store
- Other transport services
COMPLETE SWITCHGEAR DISTRIBUTION DEVICES KRP-10 VA-630...3150 U3,T3
Complete switchgears are designed for receiving and distributing electrical energy with a frequency of 50Hz, a voltage of 10(6)kV with a rated current of busbars of 630,1000,1250,1600,2000,2500 and 3150A and are operated in areas with a temperate climate + 4C°.
Climatic type U3 or T3 according to GOST 15150.
Normal operation of the switchgear is ensured under the following conditions:
1. Altitude above sea level - no more than 1000 m;
2. The environment is non-explosive, not containing conductive dust, aggressive gases and vapors in concentrations that reduce the parameters of the switchgear to unacceptable levels;
3. Atmosphere type - II according to GOST 15150.
The main technical parameters of the switchgear are given in table 1.
The classification of the cabinets is given in table 2.
In the case of a double-row cabinet, the switchgear is equipped with busbar bridges. Busbar bridges are installed only on the outer cabinets. The distance between the cabinet facades should be 2000, 2500 or 3000 mm.
Example of a switchgear entry with a HV network voltage of 10 kV at a rated tripping current of 31.5 kA, climatic version U3
KRP-10 VA-31.5 U3 TU U 3.2-14152239-008:2010
When ordering, it is necessary to fill out a questionnaire and indicate the customer's payment and shipping details.
Table 1
Parameter name |
The meaning of the parameters of the KRP type |
|||
KRP-10 VA-20 U3* |
KRP-10 VA-20 Т3* |
KRP-10 VA-31,5 U3* |
KRP-10 VA-31,5 Т3* |
|
1 Nominal voltage, kV |
6,0; 10,0 |
6,0; 10,0; |
6,0; 10,0 |
6,0; 10,0; |
2 Maximum working voltage, kV |
7,2; 12,0 |
7,2; 12,0 |
7,2; 12,0 |
7,2; 12,0 |
3 Rated current of the main circuits of KRP (switchgear) cabinets, A: |
630; 1000; 1600; 2000; 2500; 3150 |
630; 1250; 2500 |
630; 1000; 1600; 2000; 2500; 3150 |
630; 1250; 2500 |
4 Nominal current of busbars, A |
630; 1000; 1600; 2000; 2500; 3150 |
630; 1250; 2500 |
630; 100; 1600; 2000; 2500; 3150 |
630; 1250; 2500 |
|
|
|
|
|
|
|
|
|
|
5 Rated breaking current of the circuit breaker built into the KRP (switchgear), kA |
20,0 |
31,5 |
||
6 Thermal withstand current for a time interval of 3 s, kA |
20,0 |
31,5 |
||
7 Rated current of electrodynamic withstand of main circuits of KRP (switchgear) cabinets, kA |
51 |
81 |
Table 2
Classification feature |
Design of KRP (switchgear) cabinets according to this classification feature |
1 Insulation level according to GOST 1516.3 |
Normal insulation |
2 Type of insulation |
Air |
3 Presence of insulation of current-carrying parts |
With insulated busbars - for rated breaking currents of 20; 31.5 kA; With insulated busbars, taps to them and busbar inputs for rated breaking current of 31.5 ** kA |
4Terms of Service KRP (switchgear) |
With two-way service |
5 Type of control |
Local, remote |
6 Execution of inputs |
Cable; busbar |
7 Type of KRP (switchgear) cabinets depending on built-in equipment and connections |
SHVMP – cabinet with oil switch with spring drive; SHVME – with an oil switch with an electromagnetic drive; SHTN – with voltage transformers; SHPS – with power fuses; SHR – with detachable contact connections; SHKA – with combined equipment (with voltage transformers, arresters, capacitors); SHGV – blind input; SHKS – with cable assembly; SHST – with power transformers; SHSHP - busbar jumpers; SHSHV - busbar entries; SHVVE – with vacuum switch with electromagnetic drive on direct current; SHVVP – the same, with a spring drive on alternating current; SHV1…2* - busbar inserts; SHP – transitional; SHNVA – with low voltage equipment; ORSH – free-standing relay cabinet |
8 Presence of doors in KRP (switchgear) cabinets |
Cabinets with doors; cabinets without doors |
Continuation of table 2
Classification feature |
Design of KRP (switchgear) cabinets according to this classification feature |
9 Availability of retractable elements in KRP (switchgear) cabinets |
With retractable elements; without retractable elements |
10 Type of supply of KRP cabinets |
Blocks of up to three cabinets (cabinets 750 mm wide); blocks of up to two cabinets; separate cabinets |
11 Degree of protection of the KRP (switchgear) enclosure; curtains and partitions of compartments (with the withdrawable element in the rolled-out position) according to GOST 14254 |
1P20 – with the KRP (switchgear) cabinet doors closed; the working position of the withdrawable element (for KRP cabinets without doors); curtains and partitions (in cabinets with sliding elements); - 1P00 – with open doors of the KRP (switchgear) cabinet without sliding elements |
__________________________ * The numbers in the cabinet type designation depend on the arrangement of the row of substation cabinets and the rated current of the KRP (switchgear) cabinet. Note: Cabinets of the SHVVE, SHVVP type are intended for electrical installations with frequent switching operations. ** Climatic version U1 and U3 |
Questionnaire form
Nominal voltage, kV |
|
||||||
Nominal current of busbars, A |
|
||||||
Sequence number of the KRP (switchgear) cabinet |
1 |
2 |
3 |
4 |
5 |
6 |
|
Principal Electrical Schematic
|
|
|
|
|
|
|
|
KRP (switchgear) cabinet designation |
|
|
|
|
|
|
|
Purpose of the cabinet |
|
|
|
|
|
|
|
Name of vacuum circuit |
|
|
|
|
|
|
|
Name of the current transformer and their quantity |
|
|
|
|
|
|
|
Name of the 0-sequence current transformer and their number |
|
|
|
|
|
|
|
Availability of voltage transformer |
|
|
|
|
|
|
|
Protection characteristics |
МТЗ |
|
|
|
|
|
|
ТО |
|
|
|
|
|
|
|
Overload protection |
|
|
|
|
|
|
|
ZМЗ |
|
|
|
|
|
|
|
ZНЗ |
|
|
|
|
|
|
|
Differential protection |
|
|
|
|
|
|
|
Availability of AVR |
|
|
|
|
|
|
|
Availability of accounting |
|
|
|
|
|
|
|
Availability of busbar |
|
|
|
|
|
|
|
Object |
|
||||||
The customer and his address |
|
||||||
Design organization and its address |
|
||||||
Shipping details |
|
||||||
Payment details |
|